Guidelines For Testing And Troubleshooting
Fiber Optic Installations
This is
intended as an overview and installation checklist for all managers, engineers and
installers on the overall process of testing and troubleshooting a fiber optic communications
system. This document is based on the FOA books The FOA
Reference
Guide to Fiber Optics (RGFO) and The FOA Reference Guide to Premises
Cabling
(RGPC) and the FOA Online Reference Guide. You should also download a
copy of
the NECA/FOA 301 fiber optic installation standard as a reference.
1. Once
a fiber optic cable plant, network, system or link is installed, it needs to be
tested for four reasons:
a. to
insure the fiber optic cable plant was properly installed to specified industry
standards.
b. to insure the equipment intended for use on the
cable plant will operate properly
on the cabling
c. to insure the communications equipment is working
to specifications
d. to
document the cable plant and network for reference in case of future problems
2. Tools and Test Equipment Needed
The
following tools are needed to test and troubleshoot the fiber optic cable
plant, system or link properly.
a. Optical Loss Test Set or power meter and test
source with optical ratings
matching the specifications of the installed
system (fiber type and transmitter
wavelength and type) and proper connector
adapters. An OLTS that merely tests
cable plant loss may not include a calibrated
power meter needed for testing
transmitter and receiver power, so a calibrated
power meter and source are a
better choice for link or system testing.
b. Reference test cables with proper sized fiber and
connectors and compatible
mating adapters of known good quality. These do not
generally need to be
“reference quality” but only in good condition,
generally defined as having
connector losses of less than 0.5 dB.
c. Visual fiber tracer and/or visual fault locator
(VFL)
d. Connector inspection microscope with magnification
of 100-200X and fixturing for proper connectors. Video microscopes are
recommended.
e. Cleaning supplies intended specifically for the
cleaning of fiber optic connectors.
f. Optional: OTDR with long launch and receive cables
(100 m for Multimode, 1 km or more for singlemode)
3. Testing And Troubleshooting The Installed Cable Plant
All
fiber cable plants require certain basic tests to insure they were installed
correctly
and
meet expected performance values. These are guidelines for testing and
troubleshooting
the cable plant itself. The most valuable data one can have for
troubleshooting
is the installation documentation.
Note - Cleaning: Before any testing, connectors should be cleaned carefully to
ensure
that no dirt is present on the end face of the connector
ferrule as this will cause high
loss and reflectance. Protective caps on connectors, often
called “dust caps” – some
say that’s because they usually contain dust – do not
necessarily keep connectors
clean. Use cleaning supplies intended for cleaning fiber optic
connecotrs only as other
materials my leave residue or cause harm to the connectors.
3.1. What Can Go Wrong?
There
are a number of possible problems with fiber optic cable installations that are
caused
by installation practice. These include:
a. Damage to the cable during installation caused by
improper pulling techniques
(such as not pulling the fiber cable by the
strength member,) excess tension,
tight bends under tension, kinking or even too
many bends. Most of these
problems will be seen on all fibers in the cable.
b. Damage to the fibers in the cable during cable
preparation for splicing or
termination. Fibers may be broken or cracked during
cable jacket or buffer tube
removal or fiber stripping. This may affect all
fibers in the cable or buffer tube or
just one fiber.
c. High loss splices caused by improper splicing
procedures, especially poor
cleaving on mechanical splices or improper
programming of fusion splicers. Most
fusion splicers give feedback on most problems if
the operator is properly trained.
Individual fibers can be damaged when being
placed in splice trays or tubes of
fibers damaged during placement in splice
closures.
d. High loss connectors may be caused by bad
processes or damage after
termination. Adhesive/polish connectors may have
poor end finishes or cracks in
the fiber at the end of the ferrule or
internally. Prepolished/splice connectors are
generally high loss due to poor mechanical
splicing processes during termination
causing high internal loss.
3.2. Testing And Troubleshooting Steps For Installed Cable Plants
FOA Standard FOA-1: Testing Loss of Installed Fiber Optic Cable
Plant, (Insertion Loss,
TIA OFSTP-14, OFSTP-7, ISO/IEC 61280, ISO/IEC 14763, etc.)
FOA Standard FOA-4: OTDR Testing of Fiber Optic Cable Plant
(TIA FOTP-
8/59/60/61/78, ISO/IEC 14763, etc.)
FOA Standard FOA-2: Testing Loss of Fiber Optic Cables, Single
Ended, (Insertion
Loss, TIA FOTP-171, OFSTP-7, , ISO/IEC 14763)
3.2.1. Before installation, it is
advisable to test all cable as received on the reel for
continuity
using a visual tracer or fault locator. Cables showing signs of damage in
shipment
may need OTDR testing to determine if the cable itself is damaged.
Obviously,
no cable showing damage should be installed.
3.2.2. Test insertion loss after installation
a. After installation,
splicing (if applicable) and termination, all cables should be
tested for insertion loss using a source and
meter or OLTS (optical loss test set)
according to standards OFSTP-14 for multimode
fiber, OFSTP-7 for singlemode
fiber. See
FOA Standards for simplified explanations of these standards:
b. Generally cables are tested individually
(connector to connector for each
terminated section of cable and then a complete
concatenated cable plant is
tested “end-to-end”, excluding the patchcords
that will be used to connect the
communications equipment which are tested
separately.
c. It is the concatenated cable test that is used to
compare to the link power budget and communications equipment power budget to
insure proper operation.
d. Insertion loss testing should be done at the
wavelength of intended operation if
known or at two wavelengths with appropriate
sources (850/1300 nm with LEDs
for multimode fiber, 1310/1550 nm with lasers for
singlemode fiber, 1490 for
FTTH.)
e. Unless standards call for bi-directional testing,
double-ended testing with both
launch and receive cables (OFSTP-7/14) is
adequate.
f. Data on insertion loss of each fiber should be
kept for future comparisons if
problems arise or restoration becomes necessary.
Recording data on a label
inside the patchpanel or enclosure is common
practice.
g. Long cables with splices may be tested with an
OTDR to confirm splice quality
and detect any problems caused during
installation, but insertion loss testing with
an OLTS (light source and power meter) is still
required to confirm end-to-end
loss. Cables with insertion loss near expected
values do not also need OTDR
testing. Cables tested with an OTDR should have
the data kept on file for future
needs in restoration.
3.2.3. Troubleshooting
a. First determine if the problem is with one or all
the fibers in the cable. If all fibers are a problem, there is a likelihood of
a severe cable installation problem. If all fibers are broken or have higher
than expected loss, an OTDR will show the
location of the problem on longer cables but
premises cables may be too short
and need physical inspection of the cable run. If
the problem is caused by kinking
or too tight a bend, the cable will have to be
repaired or replaced. Generally OSP
cables will be spliced as in a restoration and if
the cable is a short OSP cable or
a premises cable, replaced.
b. High loss fibers have several potential causes,
but bad splices or terminations
are the most likely cause for field terminated
cables. In some cases, using
improper termination practices will result in
high loss for all fibers, just as in
kinking or bending losses, not just one fiber.
c. Testing for high loss fibers should start with
microscope inspection of
terminations for proper polish, dirt, scratches
or damage.
d. If dirt appears to be the problem, clean the
connectors and retest.
e. If other connector damage is found on visual
inspection, retermination will
probably be necessary. Sometimes scratches can be
polished out with diamond
film by an experienced technician.
f. Prepolished splice connectors with internal
splices will generally look OK when
inspected with a microscope unless damaged after
installation. The most likely
cause of loss with these connectors is high
splice loss in the internal splice. They
can be tested with a visual fault locator coupled
into the fiber at the far end. High
light loss will be seen as an illumination of the
connector ferrule. Some
connectors have translucent backshells and can be
tested with a VFL coupled
directly into the connector.
g. If the reason for high loss is not obvious and
the connectors are adhesive/polish style, the problem may be a fiber break in
the back of the connector. A VFL may help in finding fiber breaks, depending on
the connector style and the opacity of the cable jacket.
h. Cables with a fiber or fibers showing very high
loss or no light transmission at all should be tested for obvious breaks in the
pigtail fiber or cable, generally at the splice or connector, with a visual
fault locator or high resolution OTDR if the
cable is of sufficient length
i. Splice loss problems can be pinpointed during OTDR
testing. Confirmation with a VFL should be done if the length from the end of the
cable is short enough (~2-3 km) where a VFL is usable. The VFL can find high loss
splices or cracks I fibers caused by handling problems in the splice tray.
j. High loss links where the excessive loss is only
a few dB can be tested like a
patchcord with a single-ended test with a source
and power meter. When tested
in this manner, a high loss connector will show
high loss when connected to the
launch cable connector but not when connected
directly to the power meter
detector which picks up all the light from the
fiber.
3.2.4. Hints for troubleshooting
a. Having access to design specifications and
installation documentation and
specifications will greatly assist
troubleshooting.
b. If possible, interview the installer to help
uncover processes that may lead to
issues in installation, such as pulling methods,
lubrication, intermediate pulls,
splicing or termination methods (like improper
field termination of singlemode
which can lead to high loss and reflection even
when connectors look OK in a
microscope.)
3.2.5. Testing And Troubleshooting Patch cords
FOA Standard FOA-2: Testing Loss of Fiber Optic Cables, Single
Ended, (Insertion
Loss, TIA FOTP-171, OFSTP-7, , ISO/IEC 14763)
Patch
cords are short factory-terminated cables usually with standard heat-cured
epoxy/polish
connectors on each end. They are used to connect equipment to the cable
plant
and as reference cables for testing insertion loss.
3.2.5.1. Likely Problems
Most
patchcord problems are connector problems, caused by damage due to handling
or
numerous matings when used as reference cables for testing other cables.
Connectors
may also be damaged by breaking fibers at the back of the connector due
to
excess stress during handling or by placing other equipment on top of them in
enclosures
or patch panels.
3.2.5.2. Testing And Troubleshooting Steps
a. All patchcords, especially those used as
reference cables for insertion loss
testing, should be tested for insertion loss.
b. Patchcords should be tested with an optical loss
test set (optical power meter
and source) using single-ended FOTP-171 methods
with one reference cable
used as a launch cable.
c. This will test the connector mated to the
reference cable and the fiber in the
patchcord, which is short enough it should have
no measurable loss.
d. Since the connector connected to the power meter
will not be connected to fiber but presented directly to the detector of the
power meter, it effectively has no loss.
e. After testing in one direction, reverse the
patchcord and test the other end.
f. In both directions, factory-made patchcords
should have a loss of less than 0.5
or whatever performance the user has specified
with patchcord vendors.
g. High loss connectors should be inspected with a
microscope for dirt or damage.
h. If other connector damage is found on visual
inspection, retermination will
probably be necessary but may not be cost
effective, so the patchcord should be
replaced. Sometimes scratches can be polished out
with diamond film by an
experienced technician.
i. Some optical loss test sets include fiber
interfaces on both source and meter
ports, so all testing is done double-ended, even
if the cable under test is directly
connected to an input port. A test set such as
this makes reverse testing less
effective since reversing test direction may not
have any significant effect. Test
ports on an OLTS like this should be kept covered
when not in use and cleaned
periodically. Damaged fibers inside an OLTS will
require factory repair.
4. Testing And Troubleshooting Communications Equipment
FOA Standard FOA-5 Fiber Optic Datalinks
FOA Standard FOA-3: Measuring Optical Power (Transmitter and
Receiver Power,
FOTP-95, Numerous ISO/IEC standards)
After
the cable plant has been tested, the communications equipment should be
properly
connected using matching known-good patchcords. If the cable plant loss is
within
the loss budget of the equipment (including the loss of the patchcords), the
communications
link should work properly. If the link does not work, most likely potential
problems
are the following.
a.
Improper
connections
b. Cable plant problems
c. Malfunctions of communications equipment
4.1. Testing And Troubleshooting Steps For Communications Equipment
a. Improper connections. The system requires a
transmitter be connected to a
receiver, of course, so it is important to verify
this connection for each link. Even
if the cable plant is properly documented, fibers
may have been crossed at
intermediate connections, so using a visual
tracer or visual fault locator will allow
quick confirmation of the connection.
b. The functioning of the communications equipment:
i. If it is connected to the cable plant but not
operating properly, begin by
checking the power at the receiver on one end of
the link.
ii. Disconnect the cable at the receiver input and
measure power with an optical power meter. Make sure the equipment is trying to
transmit a signal. Some equipment has a testing mode to force transmission of a
test signal or the equipment may simply keep transmitting to try to complete a
connection.
iii. If the receiver power is within specifications,
the receiver or electronics
beyond the link may be the problem. Use equipment
diagnostics or consult the manufacturer for assistance.
iv. If the receiver power is too high, it may be overloading
the receiver and an optical attenuator should be inserted at the receiver end
to reduce the power to the proper level.
v. If the receiver power is lower than required by
operating specifications, the cause is either low transmitter power or too much
loss in the cable plant.
vi. To test transmitter power, disconnect the
patchcord connecting the
transmitter to the cable plant and measure the
optical power. If the power is low, there is a problem with the transmitter or
patchcord.
vii. To determine which is the problem, try testing
the transmitter with a known good patchcord. If the power is then within spec,
replace the bad patchcord and test the link again.
viii. If the transmitter power is low with a known good
patchcord, the equipment may need maintenance (cleaning) of the output port or
replacement.
ix. If the transmitter tests as good but receiver power
is low, the problem is
probably in the cable plant. First try to switch
the communications link to
spare fibers to see if that solves the problem.
Next test the loss of the suspect fibers in the cable plant with an OLTS to
determine if the cable plant loss is excessive.
c. Cable Plant Problems
i. High loss in the cable plant can be caused by
damage after installation and testing. Use a visual tracer or visual fault
locator to confirm continuity and an OLTS to test loss. See directions above on
testing the loss of the cable plant.
ii. If the cable plant is long enough (>100m), it
can be tested with an OTDR to pinpoint problems.
iii. If the cable plant loss is not the problem, there
are other possible issues related to the bandwidth of the cable plant.
iv. Multimode cable plants operating at 1300 nm with
LED sources may have bandwidth problems caused by the total dispersion due to
both chromatic and modal dispersion.
v. Multimode cable plants operating at 850 nm with
VCSEL sources on non-laser- optimized fiber (usually 62.5/125 FDDI grade fiber)
may suffer nonlinear modal dispersion that can produce distorted pulses that
will cause data transfer problems.
vi. Multimode cable plants operating at 1300 nm with
laser sources may have an improperly installed mode-conditioning patch cord
(offset-launch) or none at all.
vii. Single mode links may suffer from problems caused
by reflections at
connectors or mechanical splices.
viii. Reflections in singlemode terminations or splices
near the source may cause nonlinearities in the laser transmitter which distort
pulse shapes, causing high bit error rates (BER).
ix. Reflections near the receiver or at both ends can
cause multiple reflections in the cable that create “optical noise” that causes
BER.
x. Reflections can be tested, if the cable plant is
long enough (>100m), with an OTDR to pinpoint problems.
xi. Reflections can be reduced by introducing an
index-matching gel or fluid in the joint (Vaseline or mineral oil works, but is
messy to clean up) to see if that solves the problem.
xii. Highly reflective connectors or splices should be
replaced as soon as
possible. Remember most singlemode terminations
are made by fusion
splicing factory-terminated pigtails onto
installed cabling.
5. Update Documentation
After
completing tests, troubleshooting and repairs, update documentation to reflect
the
necessary
procedures and any changes to the network. If the fix is to switch to spare
fibers
and suspect fibers are not fixed, not that on documentation to prevent future
problems.
References
There
are other FOA Technical Bulletins that should be used as references for the
design
and planning of the network. These documents can be downloaded from the
FOA
Tech Topics website. In addition to those, we recommend:
The FOA Reference Guide to Fiber
Optics, by Jim Hayes,
published by the FOA.
The FOA Reference Guide to Premises
Cabling, by Jim Hayes,
published by the
FOA.
The FOA Reference Guide to Outside
Plant Fiber Optics, by Jim Hayes, published
by the
FOA.
FOA Online Reference Guide, FOA website, www.thefoa.org
NECA/FOA-301 Standard For Installing
And Testing Fiber Optic Cables
(NECA/FOA-301),
NECA Codes and Standards, 3 Bethesda Metro Center, Bethesda,
MD
20814 Download from FOA website
FOA Tech Bulletins (Printable Reference Documents)
Designing and manufacturing fiber
optic communications products for manufacturers of
products using fiber optics .
(PDF, 0.2 Mb)
Choosing, installing and using
fiber optic products for communications network users.
Note: This information is provided by The Fiber Optic
Association, Inc. as a benefit to
those interested in designing, manufacturing, selling,
installing or using fiber optic
communications systems or networks. It is intended to be used
as a overview and
guideline and in no way should be considered to be complete or
comprehensive. These
guidelines are strictly the opinion of the FOA and the reader
is expected to use
them as a basis for creating their own documentation,
specifications, etc. The FOA
assumes no liability for their use.